ISOLATOR TYPE

 

IS Isolator ¼±Á¤ ( Application )  

ÇÏ´Ü¿¡¼­ Àû¿ëºÐ¾ß¸¦ ¼±ÅÃÇϸé ÇØ´ç IS Isolator¿¡ ´ëÇÑ ÀڷḦ °Ë»öÇÒ ¼ö°¡ ÀÖ½À´Ï´Ù.

 
Analogue Inputs
  • 2¼±½ÄÀü¼Û±â (Tx),  4-20mA  ¹×  'Smart'
  • T/C , mV, RTD ¹× Ohm sources 
  • Vibration Transducer
  • Analogue Outputs
  • Controller Outputs (I/P converters)
  • Digital Inputs (ON/OFF, NAMUR)
  • Switches / Proximity  Detectors
  • Digital Outputs (ON/OFF, NAMUR)

  • Switch Output to Hazardous Area
  • Frequency
  • Frequency related instruments,  RS422/RS485  Isolation Repeater
  • ±âŸ
  • Fire / Smoke Detectors
  • Load cell / Strain Bridge Gauge
  • Power Supply Distribution and Diagnostic Module
  • Analogue Input - 2¼±½Ä Àü¼Û±â (Tx) ,  4-20mA Àü·ù½ÅÈ£¿ë, 'smart' ¹× 3,4¼±½Ä Àü¼Û±â

    Device

    No. of
    channels

    Input   (Hazardous)

    Output

    LFD

    SIL

    HART

    Main features

     

    Active

    Passive

    Active

    Passive

    Splitter

    Alarm

    DIN-rail mounting or Termination Board available
    D5011

    1 or 2

    ¡Ã15V

    ¡î

     

    ¡î

     

     

     

     

    SIL3

    ¡î

    12.5mm,  output 550§Ù

    D5014

    1 or 2

    ¡Ã15V

    ¡î

    ¡î

    ¡î

    ¡î

    ¡î (D)

     

     

    SIL3

    ¡î

    12.5mm,  output 550§Ù

    D5015

    1 or 2

    ¡Ã15V

    ¡î

    ¡î

    ¡î

    ¡î

    ¡î (D)

     

     

    SIL3

    ¡î

    12.5mm,  output 550§Ù

    D5212Q

    4

    ¡Ã15V

    ¡î

    ¡î (2)

    ¡î

     

    ¡î

    ¡î  (1)

     

    SIL2

     

    22.5mm,  output 300§Ù, SPDT x 1,  Modbus

    D5254S

    1

    ¡Ã15.5V

    ¡î

    ¡î

    ¡î

    ¡î

     

    ¡î  (2)

    ¡î

    SIL2

     

    22.5mm,  output 300§Ù, SPDT x 2,  Modbus

    Installation  Accessories

    D5000TB

    8 ¶Ç´Â 16 modules Termination Board,   DCS system  cableÀ» »ç¿ë

    Analogue Input - thermocouple,  mV and RTD sources
    Device No. of
    channels

    Input  from
    Hazardous area

    LFD

    SIL

    Output to Safe area Main features

    type

    SplitterI

    Alarm

    DIN-rail mounting or Termination Board available
    D5072 1 or 2

    mV, T/C, RTD, Ohm

    ¡î

    SIL2

    4-20mA Source or Sink

    ¡î (D) 1SPST photo MOS 12.5mm, Modbus
    D5072S-087 1 2,3,4 RTD, Ohm ¡î

    SIL2

    2,3,4 RTD, Ohm     12.5mm, RTD to RTD
    D5273S 1

    mV, T/C, RTD, Ohm

    ¡î

    SIL2

    4-20mA Source or Sink

      2SPST photo MOS 22.5mm,  Modbus
    Analogue Input - vibration transducer

    Device

    channels

    Input  from  Hazardous area

    LFD

    SIL

    Main features

    DIN-rail mounting or Termination Board available
    D5062S 1 0~ -20V@ 2,3 wire Vibration transducer

    X

    2

    DIP switch setting
    Analogue Output - controller outputs, I/P converters

    Device

    channels

    Output to  Hazardous area

    LFD

    SIL

    Input  from Safe area

    Main features

    DIN-rail mounting or Termination Board available
    D5020

    1  or 2

    0/4 to 20 mA, max.700 ¥Ø load. Source

    ¡î

    SIL2

    4-20mA Source

    Sourced input, Input ¡Â 2.5 V voltage drop , With HART

    Digital Input - switches / proximity detectors, NAMUR

    Device

    channels

    Output to Safe area

    Splitter

    LFD

    SIL

    Main features

    DIN-rail mounting or Termination Board available
    D5030

    1 or 2

    SPST or SPDT (relay contact) + LED

    ¡î

    ¡î

    SIL3

    12.5mm,  4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W

    D5031

    1 or 2

    SPST open-collector TR

    ¡î

    ¡î

    SIL3

    12.5mm,  100 mA at 35 Vdc (¡Â 1.5 V voltage drop).

    D5032

    1 or 2

    SPST or SPDT (relay contact) + LED

    ¡î

    ¡î

    SIL3

    12.5mm,  100 mA 50 Vdc 5 W , Termination board Use Only

    D5034

    1 or 2

    Transparent Namur of input status

     

    ¡î

    SIL3

    12.5mm,  V max. 30 V, current limited at ≈ 8 mA

    D5036

    1 or 2

    SPST or SPDT (relay contact) + LED

     

    ¡î

    SIL2

    12.5mm,  4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W,  No G3

    D5037

    1 or 2

    SPST open-collector TR

     

    ¡î

    SIL2

    12.5mm,  100 mA at 35 Vdc (¡Â 1.5 V voltage drop)., No G3

    D5231E

    8

    SPST open-collector TR

    ¡î

    ¡î

    SIL2

    22.5mm,  100 mA at 35 Vdc (¡Â 1.0 V voltage drop), Logical output, MODBUS

    D1130

    1 or 2

    SPST or SPDT (relay contact) + LED

    ¡î

    ¡î

    SIL2

    22.5mm,  AC supply

    Digital Output

    Device

    channels

    Output  to Hazardous area

    LFD

    SIL

    POWER

    Main features

    DIN-rail mounting or Termination Board available
    D5040 1 or 2

    15~17.5V/35mA(176.3§Ù~238.7§Ù),
    19.5~20.5V/70mA(88.2§Ù~101.4§Ù)

      SIL3

    Loop Powered

    24 Vdc nom (18~30Vdc) Input,  0.75 W with 24 V supply ,NE Loads

    D5048S 1

    8.5~13V, 45 mA(174§Ù~275§Ù)

    ¡î SIL3

     Loop Powered

    24 Vdc nom (20~30Vdc) input, Override,  1.1 W with 24 V supply ,NE Loads

    D5049S 1

    8.5~13V, 45 mA(174§Ù~275§Ù)

    ¡î SIL3

    Bus Powered

    Switch contact(5.0V ¡Â¡Ã 20.0V) input , Override,  1.1 W with 24 V supply ,NE Loads

    D5240T 3

    14~17V/35 mA(176.3§Ù~278.3§Ù),
    14~16V/70 mA(108§Ù~139.2§Ù),
    13.5~17.5V/105mA(58.8§Ù~92.8§Ù)

      SIL2

    Bus Powered

    Switch contact(5.0V ¡Â¡Ã 18.0V) input,  3.3 W with 24 V supply , MODBUS ,NE Loads

    D5244 1 or 2

    IS. voltage free SPDT relay contact

      SIL2,3

    Ext. Powered

    24 Vdc nom (18~30Vdc) input, 0.4 W with 24 V supply ,NE Loads

    Frequency Input / RS422, RS485 Reapeater

    Device

    channels

    Input from hazardous area

    Main features

    DIN-rail mounting
    D1035S
    1
    Magnetic pick-up, contact, proximity to EN60947-5-6, open collector TR to frequency signals up to 50KHz, TTL CMOS

    22.5mm,  KR type approval

    D1060S
    1
    RS422/ RS485 signal

    22.5mm,  Modbus, Fieldbus, Profibus and all other RS485 protocols

    Smoke Detector / Flammable Liquid Presence Detector
    Device channels Output to hazardous area

    Output to Safe  area

    Main features

    DIN-rail mounting
    D1022 1 or 2

    1 to 40mA,  4-20mA output on load of 100 to 600 ohm

     

    Input signal to Safe area : 6 to 30V loop powered,  1 to 40mA,   9.5V @ 20mA voltage drop with 500 ohm load

    D1080D 2

     

    Voltage free 2 x SPDT relay contact, 2A 250Vac

    Input from hazardouse area : 13.0V 150§Ù typical,  0 to 14mA, DIP switch settable

    Load cell / Strain Gauge Bridge Isolating Repeater

    Device

    No. of
    channels

    Input from
    hazardous area

    Output to
    safe area

    SIL

    Main features

    DIN-rail mounting
    D5263S 1 Up to 4 x 350 ohm load cell, or 5 x 450 ohm load cell, or 10 x 1,000 ohm load cells can be connected in parallel

    same as input
    impedance : 500 ohm typical
    Excitation voltage : ¡Ã4.0V typcial, ¡Â 15V max. Externally applied

    SIL2

    A/D conversion : 12.5ms
    Bridge supply voltage : 4.0Vdc nominal,   1 to 4mV/V Bridge output signal
    Line resistance compensation : ¡Â 10 §Ù

    D5264S 1 Up to 4 x 350 ohm load cell, or 5 x 450 ohm load cell, or 10 x 1,000 ohm load cells can be connected in parallel

    0/4-20mA on max 300 ohm load @ 24mA
    Modbus RS-485

    SIL2

    Response time :  ¡Â 20ms (10-90% step)
    Bridge supply voltage : 4.0Vdc nominal,   1 to 4mV/V Bridge output signal
    1x Trip Alarm SPST 100mA, 60Vdc

    Power Supply Distrubution and diagnostic module
    Device No. of
    channels
    Power

    SIL

    Main features

    DIN-rail mounting or Termination Board available
    D5202S 1 Single or Redundant,  24Vdc supply in groups of 4A each into the power bus

    SIL3

    Supply current to approximately 40-50 D5000 modues,  Operation temp : -40 to +70 °C
    5 LED indicates power presense, supply variance, supply faults, common bus fault
    2 replaceable 5x20, 6A fuses